Emerson Network Power and the Emerson Network
Power logo are trademarks and service marks of
Emerson Electric Co. ©2014 Emerson Electric Co.
Specifications
While every precaution has been taken to ensure
accuracy and completeness in this literature, Liebert
Corporation assumes no responsibility, and disclaims
all liability for damages resulting from use of this
information or for any errors or omissions.
© 2014 Liebert Corporation. All rights reserved
throughout the world. Specifications subject to
change without notice.
All names referred to are trademarks or registered
trademarks of their respective owners.
® Liebert is a registered trademark of the Liebert
Corporation.
SL-30600 (R06/14) Printed in USA
EmersonNetworkPower.com
Emerson Network Power
Global Headquarters
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
800 877 9222 Phone
(U.S. & Canada Only)
614 888 0246 Phone
(Outside U.S.)
Contact@EmersonNetworkPower.com
Emerson Network Power
Caribbean and Latin America
Office – United States of America
+1-954-984-3452 Phone
Emerson Network Power
Canada
3580 Laird Rd Unit 1
Mississauga
Ontario L5L 5Z7
+1 905 569 8282
Ask@EmersonNetworkPower.com
Liebert
®
NXL™ UPS Model Size 250 kVA 300 kVA 400 kVA 500 kVA 625 kVA 750 kVA 800 kVA
Input AC Parameters
Input Voltage to Rectifier 480, 575, 600 VAC 3-phase, 3-wire
480 VAC
3-phase,
3-wire
480, 575, 600 VAC
3-phase, 3-wire
480 VAC 3-phase,
3-wire
Input Voltage to Bypass
480, 575, 600 VAC 3-phase,
3- or 4-wire
480 VAC
3-phase, 3-
or 4- wire
480, 575, 600 VAC
3-phase, 3- or 4-wire
480 VAC 3-phase,
3- or 4- wire
Input Voltage Range +10%, -15% (-30% battery assist)
Input Frequency 60 Hz
Permissible Input Frequency Range 55 to 65 Hz
Input THDi at nominal voltage at full load <10% <5%
Power Walk-In 1 to 30 (selectable) in 1 sec. Increments
Battery & DC Parameters
Battery Type VRLA (Valve Regulated Lead Acid) or FLA (Flooded Lead Acid) or Liebert FS Flywheel
Nominal Battery Bus 480 VDC
Battery Float Voltage 540 VDC
Available Recharge Power (with 100% load) 34 kW 40 kW 54 kW 67.5 kW 30 kW 100 kW 40 kW
DC Ripple Voltage in Float
and Const V Ch. mode
<1 (RMS value) <3.4% Vpp
Temperature Compensated Battery Charging
Standard (with temperature probe)
Output Parameters
Inverter Type IGBT PWM Control
Output Power 250 kVA 300 kVA 400 kVA 500 kVA 625 kVA 750 kVA 800 kVA
Output Power 225 kW 270 kW 360 kW 450kW 625 kW 675 kW 800 kW
Output Voltage 480, 575, 600 VAC 480 VAC 480, 575, 600 VAC 480VAC
Output Voltage Regulation <1% (3-phase RMS average)
Output Voltage Regulation (50% Unb. Load)
<2% (3-phase RMS average)
Output Frequency 60 Hz
Output Frequency Regulation ± 0.1%
Output THD at Nominal Voltage (Linear Load)
<2%
Output THD at nominal voltage Including a
100kVA Non Linear Load per EN 62040-3
2.5% (max)
Efficiency Up to 94% Up to 92% Up to 94%
Trancient Recovery Within 1% of nominal voltage within 16 milliseconds for 100% step load for a single module system
Voltage Displacement 120 deg +/- 1 deg (50% unbalanced load)
Unbalanced loads current capacity 50% of nominal phase current
Overload
110% for 60 minutes
125% for 10 minutes
150% for 1 minute
200% for 200ms
Physical Characteristics
Width, with Static Bypass
71.8 in
(1,823 mm)
@480VAC
78.5 in
(1,993 mm)
78.5 in
(1,993 mm)
@480VAC
111.6 in
(2,835 mm)
140.5 in
(3,568 mm)
184.8 in
(4,694 mm)
Width, without Static Bypass -
111.6 in
(2,835 mm)
125 in
(3,175 mm)
164.8 in
(4,186 mm)
Height 76.8 in (1,950 mm) 78.7 in (1,999 mm)
Weight, unpackaged, with Static Bypass
3,965 lb
(1,798 kg)
@480 VAC
4,690 lb
(2,127 kg)
@480 VAC
5,250 lb
(2,381kg)
@480 VAC
9,450 lb
(4,286 kg)
13,200 lb
(5,987 kg)
16,120 lb
(7,312 kg)
Weight, unpackaged, without Static Bypass -
9,200 lb
(4,173 kg)
12,800 lb
(5,806 kg)
15,010 lb
(6,808 kg)
Color Black, RAL 7021
Protection Class, UPS Enclosure NEMA 1, IP 20 (with and without front door open)
Standards
Transportation ISTA Procedure 1H
Standards & Conformities UL 1778 4th Edition; CSA 22.2 107.3; FCC Part 15, Class A; ANSI C62.41 B3